Mechanical Equipment - Equipment Management Program 3.11
McNeese State University
Vice President of Business Affairs
Office of Environmental, Health, Safety & Hazardous Waste
1.0Purpose:
- To ensure that good maintenance practices are carried out to facilitate the efficient operation of all
building equipment.
-
2.0Responsibility
- It is the responsibility of maintenance personnel at McNeese State University to carry out routine,
scheduled, preventive, and emergency maintenance on chillers, boilers, heating, ventilation and air conditioning systems.
-
3.0General Guidelines
- 3.1
- Chillers
- 3.1.1
- Actions essential for the proper and efficient operation of chillers should address the following items:
- 3.1.1.1
- Checking for leaks and proper purge system operation.
- 3.1.1.2
- Brushing condenser tubes of water-cooled open tower systems.
- 3.1.1.3
- Checking condition levels of refrigerant and oil.
- 3.1.1.4
- Checking chiller safety devices.
- 3.2
- Heating, Ventilation, and Air Conditioning System Maintenance (HVAC)
- 3.2.1
- To ensure that HVAC systems work at peak efficiency, maintenance personnel should:
- 3.2.1.1
- Maintain building temperatures within recommended guidelines.
- 3.2.1.2
- Check, adjust, calibrate, and repair all controls such as thermostats, controllers, valve and damper operators.
- 3.2.1.3
- Replace dirty filters and keep economizer dampers clean.
- 3.2.1.4
- Keep all heating and cooling coils clean.
- 3.2.1.5
- Eliminate duct work leaks at joints and flexible connections.
- 3.2.1.6
- Keep ducts adequately insulated.
- 3.2.1.7
- Repair or replace defective dampers.
- 3.2.1.8
- Check, adjust, or replace fan belts.
- 3.2.1.9
- Lubricate all bearings and other friction joints.
- 3.2.1.10
- Inspect fan wheels and blades for dirt accumulation and clean them as required.
- 3.2.1.11
- Adjust or repair packing glands and seals on valve stems and pumps.
- 3.3
- Boilers
- 3.3.1
- Maintenance personnel should:
- 3.3.1.1
- Continuously survey the steam system to identify and repair all steam leaks.
- 3.3.1.2
- Use acoustic or temperature probes to find non-visible leaks.
- 3.3.1.3
- Perform frequent boiler tune-ups.
- 3.3.1.4
- Inspect and repair steam traps periodically.
- 3.3.1.5
- Inspect insulation on pipes and pressure vessels periodically.
- 3.3.1.6
- Periodic inspection of condensate system.
- 3.3.1.7
- Repair or replace worn or damaged insulation, tanks, valves, strainers, and piping.
- 3.4
- Testing
- 3.4.1
- Test procedures are according to manufacturer's recommendations and suggested schedules.
- 3.4.2
- Documentation of testing is kept in the HVAC Department.
- 3.4.3
- Testing should be of a non-destructive nature and may included, but are not limited to, the following approved methods:
- Vibration
- Infrared
- Megger
- Ultrasonic
- Radiography
- Liquid Penetrant
- Magnetic Particle
- Eddy Current
- 3.5
- Training
- 3.5.1
- Employees involved in routine or preventive maintenance on mechanical may receive either formal or on-the-job training in the various areas related to the program.
- 3.5.1.1
- Documentation of training is kept by the HVAC foreman in the Central Plant.
- 3.6
- Equipment Inventory
- 3.6.1
- An inventory of mechanical and electrical equipment in the program has been established. See Appendix A.
- 3.6.1.1
- This list is a "living" document and may be added to, deleted from, and/or modified at any time.
-
4.0Routine Maintenance
- 4.1
- Chillers
- 4.1.1
- Daily
- 4.1.1.1
- Log all operating parameters.
- 4.1.1.2
- Listen for unusual noises and vibrations.
- 4.1.1.3
- Check oil levels and look for oil leaks.
- 4.1.1.4
- Check purge unit on low-pressure machines for excessive run time.
- 4.1.2
- Annually
- 4.1.2.1
- Annual inspection shall be done by maintenance personnel along with an outside service contractor.
- 4.1.2.2
- Open condensers and brush tubes.
- 4.1.2.3
- Leak check machine.
- 4.1.2.4
- Inspect starter and check points for pitting.
- 4.1.2.5
- Replace oil and oil filters
- 4.1.2.6
- Collect oil samples for analysis on all machines.
- 4.1.2.7
- Replace refrigerant filters.
- 4.1.2.8
- Check for correct operations and clean purge units.
- 4.1.2.9
- Check all safety devices for correct operation.
- 4.1.2.10
- Check electronic sensors for accuracy.
- 4.1.2.11
- Run machine and log all operating parameters.
- 4.2
- Boilers
- 4.2.1
- Daily
- 4.2.1.1
- Read all gauges and record readings on log sheet.
- 4.2.1.2
- Check operational water level.
- 4.2.2
- Semi-annual
- 4.2.2.1
- Check control linkages for the burner.
- 4.2.2.2
- Manually trip low water cutoff and check its operation.
- 4.2.2.3
- Check air inlet for obstructions.
- 4.2.2.4
- Check valves on gas train for proper operation and leaks.
- 4.2.3
- Annually
- 4.2.3.1
- Check all safety devices for correct operation.
- 4.2.3.2
- Disassemble low water cutoff and check it operation and general condition.
- 4.2.3.3
- Inspect water-side of boiler and clean if necessary.
- 4.2.3.4
- Check burner settings and adjust as necessary.
- 4.2.3.5
- Inspect fire-side and clean if necessary.
- 4.2.3.6
- Check expansion tank and sight glass for proper air cushion.
- 4.3
- Cooling Towers
- 4.3.1
- Weekly
- 4.3.1.1
- Two to three times per week ensure that conductivity level is correct and automatic blow down is operating properly.
- 4.3.1.2
- Conduct water analysis to ensure corrosion protection is present.
- 4.3.1.3
- Conduct walk-around inspection to verify proper operation.
- 4.3.2
- Annually
- 4.3.2.1
- Drain and clean cooling towers.
- 4.3.2.2
- Clean hot basins, spray nozzles, and fill.
- 4.3.2.3
- Clean strainers.
- 4.3.2.4
- Inspect towers for rust.
- 4.3.2.5
- Check and repair float valve if necessary.
- 4.3.2.6
- Check fan rotation for imbalance.
- 4.3.2.7
- Grease fan motor.
- 4.4
- Air Conditioning
- 4.4.1
- Window Units
- 4.4.1.1
- Clean or replace evaporator air filter on a quarterly basis.
- 4.4.1.2
- Check for correct operation and make necessary repairs.
- 4.4.2
- DX Units
- 4.4.2.1
- Clean or replace evaporator filter on a quarterly basis.
- 4.4.2.2
- Check for correct operation and make necessary repairs.
- 4.4.3
- Air Handlers
- 4.4.3.1
- Replace air filters on a quarterly basis.
- 4.4.3.2
- Grease fan shaft and motor bearings on a quarterly basis.
- 4.4.3.3
- Check condition of coils and condensate pans. Clean as needed
- 4.5
- Air Compressors
- 4.5.1
- Annually
- 4.5.1.1
- Replace oil.
- 4.5.1.2
- Replace filters.
- 4.5.1.3
- Inspect starter contacts and replace as necessary.
- 4.5.1.4
- Check alternating control on duplex units for correct operation.
- 4.5.1.5
- Check pressure control for correct operation.
- 4.5.1.6
- Check discharge air on each compressor to ensure that compressor is not passing oil.
- 4.5.1.7
- Check refrigerated air dryer for proper operation and service as per manufacturer's recommendation.
- 4.6
- Circulating Pumps
- 4.6.1
- Grease pump motor quarterly as per manufacturer's recommendation.
-
5.0Preventive Maintenance
- 5.1
- Preventive Maintenance Guidelines
- 5.1.1
- Preventive maintenance on mechanical equipment shall follow manufacturer's guidelines and suggested schedules.
- 5.1.1.1
- A schedule of work activity has been developed for equipment serviced by the University's HVAC Department.
- 5.1.1.2
- PM work orders are generated by computer software at the Physical Plant office.
- 5.1.2
- PM schedule is overseen by the HVAC foreman.
- 5.1.2.1
- Documented service logs are kept at the University's Central Plant.